Article Number:
At the temperature multiplexer TAMP4-G3 up to 4 PT100 sensor can be connected. These are operated as a 2-wire with 1.5 mA constant current.
By a master control can be one of 4 inputs are activated and as an analog signal at the output of AA (4..20 mA) is output. The active input is selected by two address bits according to the formula:
Input channel = 2 * bit1 + 1 * bit0
The connections are made via plug-in screw terminals up to max. 1.5 mm².
TAMP4-G3 is contactless and maintenance free. It must be protected from moisture and heavy soiling.
Technical Data:
Power supply U V = 24 V DC / 0,1 A
Housing B x H x T 70 x 86 mm x 60 mm
DIN Rail mounting
Protection IP 20
Ambient temperature -40°C ... +75°C
Temperatur sensor PT100 in 2-Leitertechnik
Temperature range -50°C C ... +150°C
Tolerance < ± 2°C
Measuring current ca. 1,5 mA
Output 4 ... 20 mA (≤ 500 Ω) max. 10 V
Error detection output < 4 mA